This air insulated ring main unit uses a vacuum circuit breaker (VCB) as the T-off. It is rated 12 kV and 630 A and is available for outdoor and indoor use.
The short-time current rating is 40 kA at 12 kV for 3 seconds, tested in CPRI. Load breaking and closed-loop breaking currents are both 630 A at 12 kV, also tested in CPRI.
Technical data
| Rated Voltage | 12kV |
| Rated Current | 630A |
| Rated short-time Current | 40kA at 12kV tested in CPRI, 3sec |
| Rating Making Current | 40kA at 12kV tested in CPRI |
| Rated Load Breaking Current | 630A at 12kV tested in CPRI |
| Rated Closed-loop Breaking Current | 630A at 12kV tested in CPRI |
| Rated Cable and Line charging breaking Current | 16A |
| Transformer off- Load Breaking Current | 10A |
| Rated Ligtning Impulse withstand Voltage | As Per IEC 62271 at 12kV tested in CPRI |