The Type ILS indoor load break switch is made for 12/24/36 kV systems and is rated for 630 A. Short-time current ratings are 40 kA, 31.5 kA or 25 kA.

It can be operated manually or by motor, and is mounted indoors in a panel, on a wall or on a structure. The fuse rating is selected based on the transformer rating.

Higher current ratings and motor-operated switches are available on request.

Technical data

Rated Voltage12/24/36kV
Rated Current630A
Rated short-time Current40kA/31.5kA/25kA
Rating Making Current20kA at 12kV tested in CPRI, 3sec
Rated Ligtning Impulse withstand VoltageAs Per IEC 62271
Rating of FuseFuse rating selection based on the transformer rating
Type of OperationManual / Motor Operated
Type of switch mounting methodIndoor - panel / wall/ structure mounting